2.2 Terminal connection
Power supply connection 1
See chapter 11 "Technical data"
Connection of outputs OUT1/2 2
Relay outputs (250V/2A),
potential-free changeover contact
Connection of outputs OUT3/4 3
a relay (250V/2A), potential-free
changeover contact
universal output
b current (0/4...20mA)
c voltage (0/2...10V)
d transmitter supply
e logic (0..20mA / 0..12V)
Connection of input INP1 4
Input mostly used for variable x1 (pro-
cess value)
a thermocouple
b resistance thermometer (Pt100/ Pt1000/ KTY/ ...)
c current (0/4...20mA)
d voltage (0/2...10V)
Connection of input INP2 5
f heating current input (0..50mA AC)
or input for ext. set-point (0/4...20mA)
g potentiometer input for position
feedback
Connection of input INP3 6
As input INP1, but without voltage
Connection of inputs di1, di2 7
Digital input, configurable as switch or
push-button
Connection of inputs di2/3 8 (option)
Digital inputs (24VDC external), gal
-
vanically isolated, configurable as
switch or push-button
Electrical connections
KS 90-1p / KS 92-1p 7 Terminal connection
6
9
10
11
12
13
14
15
1
2
3
4
5
6
7
8
9
10
11
12
13
14
17
(16)
L
N
+
5
4
3
2
1
8
7
15
2 OUT1/2 heating/cooling
L
N
+
_
SSR
3
4
5
6
9
10
11
12
13
14
15
1
2
3
4
5
8
9
10
11
12
13
14
15
17
(16)
2
1
8
7
6
7
Logik
5 INP2 current tansformer