64
If the relay is connected to a
high impedance AC device,
the snubber network used to
protect the relay contact may
cause the output to appear
to be activated when the
relay is off. To cure the
problem, cut the snubber
resistor for the output that is
being affected.
Resistor Relay
R1, R2 Relay A
R3, R4 Relay B
R5 Relay C
R6 Relay D
FIGURE A-3 - SPDT RELAY/SSR DRIVER OUTPUT BOARD