Input Specifications
THERMOCOUPLE
TYPE RANGE TYPE RANGE
J 0 to 760C E 0 to 750C
0 to 1400F 0 to 1400F
K 0 to 1360C B 200 to 1800C
0 to 2500F 400 to 3300F
T -220 to 400C N 0 to 1300C
-330 to 750F 0 to 2370F
R 200 to 1650C C 200 to 2300C
400 to 3000F 390 to 4170F
S 200 to 1650C
400 to 3000F
MILLIAMPS MILLIVOLTS RTD
4-20 mADC 0 TO 25 mV 100 OHM
(with resistor) 0 to 50 mV (.00385 OHMS/OHM/C)
10 to 50 mV -140 to 400C
VOLTS REMOTE SETPOINT
0 to 5 VDC 0 to 5 VDC
1 to 5 VDC 1 to 5 VDC
CONTROL ADJUSTMENTS
Proportional Band 1 to 3000 units
Manual Reset -1500 to 1500 units
Auto Reset (Integral) 0.0 to 100.0 repeats per minute
Rate (Derivative) 0.0 to 10.0 minutes
Cycle Time 1 to 240 seconds
Position Proportioning
Sensitivity 0.0 to 50.0%
On/Off Hysteresis 0 to 300 units
(width of hysteresis band)
First Output Position -1000 to 1000 units
Second Output Position -1000 to 1000 units
Automatic User selectable to transfer from manual to
Transfer Function automatic control when setpoint is reached
Can be disabled.
Auto/Manual Bumpless transfer from automatic to manual.
Manual Output 0 to 100%