Multi-Temperature-Controller KS 800
5.6 Input circuit examples
5.7 Digital inputs
KS 800 contains 4 digital inputs, which can also be configured individually as inputs, unless requi-
red as controller outputs (cooling output with three-point controllers or closed output with three-point
stepping controllers).
The inputs are "high-active" and designed as current sink according to IEC 1131 type 1. The current
requirement is approx. 5 mA.
Logic "0" = -3...5 V
Logic "1" = 15...30 V
With configuration as input, the following allocation is applicable:
IN/OUT13: control parameter set 1/2 switch-over
This input is used to activate the 2nd control parameter set in common with all con-
trollers which are configured accordingly.
IN/OUT14: controller switch-off
This input is used for common switch-over of all controllers configured accordingly to
manual mode and for setting the outputs to "0". All other configured functions
continue operating normally.
See also hint on page 21.
IN/OUT15: Input for leakage current monitoring
The logic signal of an external leakage current monitor can be connected to this
input.
IN/OUT16: W/W2 switch-over
This input is used for activating the 2nd setpoint (W2) with all controllers configured
accordingly.
Unused digital inputs need not be connected.
9499 040 49111 17
Komentarze do niniejszej Instrukcji