Multi-Temperature-Controller KS 800
8.2.3 COM2 interface
Address and Baudrate for the COM2 interface can be adjusted via hardware or software for each
KS 800.
Via hardware, the address is adjustable within ”01” and ”99”. In position ”00”, the address stored in
EEPROM which can be changed via software will be used when switching on. Priority is given to
the address adjusted via switch position. This address and baudrate cannot be readout or changed
via software.
The same applies to the Baudrate: in Position ”0”, the EEPROM Baudrate is effective at first. This
address can be changed via software. The digits on the switch correspond to the values used for
determination of the Baudrate during configuration in C902.
Switch position RS485 CANbus
0 from EEPROM or via software from EEPROM or via software
1 2400 Bd 20 kBd
2 4800 Bd 125 kBd
*
)
3 9600 Bd 500 kBd
*
)
4 19200 Bd 1 Mbd
5 invalid setting 10 kBd
6 invalid setting 50 kBd
7 invalid setting 250 kBd
*
)
8 invalid setting 800 kBd
9 invalid setting invalid setting
As the baudrate is adjusted automatically with the PROFIBUS DP-version, manual adjustment is
omitted.
*
) Only these Baudrates are available for DeviceNet. With faulty switch position 125 kBd is set
automatically.