Multi-Temperature-Controller KS 800
6 Outputs
(For the complete connecting diagram, see section 7.2, 7.3)
6.1 Controller outputs:
Dependent of controller configuration, various output functions are possible:
2-pnt. controller
signaller
1 output
1
)
3-pnt. controller
signaller
2 outputs
2
)
3-pnt. stepping
controller
OUT 1 heating (contr. 1) heating (contr. 1) open (contr. 1)
OUT 2 heating (contr. 2) heating (contr. 2) open (contr. 2)
OUT 3 heating (contr. 3) heating (contr. 3) open (contr. 3)
OUT 4 heating (contr. 4) heating (contr. 4) open (contr. 4)
OUT 5 heating (contr. 5) heating (contr. 5) open (contr. 5)
OUT 6 heating (contr. 6) heating (contr. 6) open (contr. 6)
OUT 7 heating (contr. 7) heating (contr. 7) open (contr. 7)
OUT 8 heating (contr. 8) heating (contr. 8) open (contr. 8)
OUT 9 switched off cooling (contr. 1) closed (contr. 1)
OUT 10 switched off cooling (contr. 2) closed (contr. 2)
OUT 11 switched off cooling (contr. 3) closed (contr. 3)
OUT 12 switched off cooling (contr. 4) closed (contr. 4)
IN/OUT 13 input or unused cooling (contr. 5) closed (contr. 5)
IN/OUT 14 input or unused cooling (contr. 6) closed (contr. 6)
IN/OUT 15 input or unused cooling (contr. 7) closed (contr. 7)
IN/OUT 16 input or unused cooling (contr. 8) closed (contr. 8)
1
) Outputs OUT1 to OUT8 are the "signal outputs".
2
) Outputs OUT1 to OUT8 are the "signal outputs 1" and the outputs OUT9 to OUT16 are the
"signal outputs 2".
KS 800 has max. 19 outputs with identical specification:
Transistor outputs, + switching (for loads with common minus connection).
Rated output current:< 70 mA, short-circuit proof
Voltage drop with full load: typ. 0,3 V, max. 1,0 V
OUT1...OUT12 12 fixed logic outputs (controller outputs). The controllers and control-
ler output allocation are fixed. Reconfiguration is not possible.
IN/OUT13...IN/OUT16 4 variable inputs/outputs. They can be configured as controller outputs
(logic outputs) or digital inputs.
9499 040 49111 19